    Concrete / Two-way slabs

    Two-way slab calculator

    The static moment, the panel split, the column-strip share and the punching check at the column — the four numbers a two-way slab design turns on. The direct design method from §8.10, with the punching coefficients from §22.6 named.

    Panel6.0 × 6.0 mAspect1.00PunchingPass
    Static moment M₀
    235 kN·m
    ln 5600 mm
    Negative moment
    153 kN·m
    0.65 M₀ interior
    Column strip
    115 kN·m
    75% of the negative
    Punching
    69%
    0.93 / 1.36 MPa
    Design moments
    Direct design method, interior panel coefficients.
    Design moments
    QuantityValueUnit
    Clear span5600mm
    Total static moment M₀235.2kN·m
    Negative moment152.9kN·m
    Positive moment82.3kN·m
    Column strip negative114.7kN·m
    Middle strip negative38.2kN·m
    Steel required at column strip1.032e+4mm²/m
    Critical perimeter2280mm

    ACI 318-19 §8.10 direct design method: valid for three or more spans, a long/short ratio ≤ 2 and live load ≤ 2× dead.

    Inspect the model
    Choose a quick result view, a scaled comparison, or the complete diagnostic set.
    Punching utilisation against span
    The column reaction grows with the tributary area, the perimeter does not.
    Punching utilisation against span0.00034.5469.08103.62138.16172.704 m4 m5 m5 m6 m6 m7 m7 m8 m8 m9 m9 m%
    Canonical equations
    The exact relationships implemented by this engine.

    M₀ = wu · l2 · ln² / 8 · Total moment in the panel, both directions.

    vu = Vu / (bo · d) · bo is the perimeter at d/2 from the column.

    vc = min(0.33, 0.17(1+2/β), 0.083(2+αs·d/bo))√f'c · ACI 318 §22.6.5.2; φ = 0.75.

    engineering methodology

    A clear path from inputs to results.

    A two-way slab carries load in both directions, and the design turns on four numbers: the static moment, how it splits between negative and positive, how much of it the column strip takes, and whether the column punches through. This gives all four.

    Step-by-step methodWorked exampleAssumptions explained

    How to use

    1. Enter the panel spans, thickness and effective depth.
    2. Set the ultimate load and the column size and position.
    3. Read the moments, the column-strip share and the punching utilisation.

    The formula

    M0=wul2ln28,vu=Vubod≤ϕvcM_0 = \frac{w_u l_2 l_n^2}{8}, \qquad v_u = \frac{V_u}{b_o d} \le \phi v_c

    Reference: ACI 318-19 §8.10 (direct design method) and §22.6.5.2 (punching).

    Worked example

    6 × 6 m panel, 200 mm slab, 10 kPa

    Inputs
    • 400 mm square interior column, d = 170 mm, f'c 30 MPa.
    Calculation path
    1. 1

      ln = 5.6 m, M₀ = 235 kN·m. Negative 153 kN·m, positive 82 kN·m, column strip 115 kN·m. bo = 2,280 mm, vu = 0.93 MPa against φvc = 1.36 MPa.

    Result

    M₀ 235 kN·m; punching at 69% — a 200 mm slab works at this span.

    Interpreting the result

    Punching, not flexure, usually sizes a flat plate. The perimeter grows linearly with the column size while the reaction grows with the square of the span, so long spans fail in punching first.

    Assumptions & limitations

    • Three or more spans, long/short ≤ 2, live ≤ 2× dead.
    • Interior-panel coefficients 0.65 and 0.35.
    • Column strip takes 75% of the negative moment.
    • Minimum thickness for deflection is not checked.

    Frequently asked questions

    When can I not use the direct design method?

    With fewer than three spans, an aspect ratio above 2, or a live load more than twice the dead load.

    What if punching fails?

    Increase the depth, the column size, or add shear reinforcement — in that order of cost.

    Why does the column strip take 75%?

    Because the slab is stiffest over the column line and sheds moment there; the middle strip takes the rest.

    Does this design the reinforcement?

    It gives the area required at the column strip; detailing and bar selection follow the code rules.

    Methodology last reviewed 2026-10-22. Results are informational and not financial or engineering advice — see our disclaimer.