Shear wall calculator
The in-plane shear strength of a reinforced concrete wall: the concrete contribution including the axial term, the horizontal steel contribution, and the design strength against the demand — with the minimum reinforcement ratio checked.
| Component | Value | Unit |
|---|---|---|
| Concrete Vc | 546.9 | kN |
| Horizontal steel Vs | 504.0 | kN |
| Nominal Vn | 1050.9 | kN |
| Design φVn | 788.2 | kN |
| Demand | 400 | kN |
| Minimum ρh | 0.20 | % |
ACI 318-19 §11.5.3: Vc = 0.17·λ·√f'c·h·d + Nu·d/(4·lw), φ = 0.75.
Vc = 0.17·λ·√f'c·h·d + Nu·d/(4·lw) · Nu positive in compression.
Vs = ρh · h · d · fy · Horizontal reinforcement only.
φVn = 0.75 (Vc + Vs) · ACI 318-19 §11.5.3.
A clear path from inputs to results.
A shear wall resists lateral load in its own plane, and its strength comes from two sources: the concrete, which gains capacity from axial compression, and the horizontal reinforcement. This separates the two and checks the minimum steel ratio.
How to use
- Enter the wall length, thickness and effective depth.
- Set the concrete and steel strengths and the axial compression.
- Compare the design shear with the demand, and check the reinforcement ratio.
The formula
Reference: ACI 318-19 §11.5.3; minimum horizontal steel §11.6.2.
Worked example
3 m × 200 mm wall, 500 kN axial, 0.25% steel
- f'c 30 MPa, fy 420 MPa, d = 2,400 mm, 400 kN shear demand.
- 1
Vc = 0.17 × 5.477 × 200 × 2400 + 500,000 × 2400/(4 × 3000) = 447 + 100 = 547 kN. Vs = 0.0025 × 200 × 2400 × 420 = 504 kN. φVn = 0.75 × 1,051 = 788 kN.
788 kN capacity against 400 kN demand — 51% utilised.
Interpreting the result
Axial compression is worth real shear capacity, which is why a wall in a tall building performs better than the same wall tested alone. Net tension removes the benefit entirely.
Assumptions & limitations
- In-plane shear only.
- Axial force is compression; tension needs the tension provisions.
- No boundary-element or stability check.
- Slender walls also need Ch. 11 and Ch. 18 checks.
Frequently asked questions
Why does compression increase shear strength?
It delays diagonal cracking; the Nu·d/(4lw) term is the code’s linearisation of that effect.
Does this cover seismic walls?
No — special structural walls need the Ch. 18 provisions, including boundary elements and the shear amplification.
What is the minimum horizontal steel?
ρ = 0.0020 for bars up to No. 16 and 0.0015 for larger, in each direction.
What depth should I use?
d = 0.8·lw is common for a wall with a concentrated end zone; use the actual distance to the centroid of the tension steel where it is known.
Methodology last reviewed 2026-10-22. Results are informational and not financial or engineering advice — see our disclaimer.