    Electrical / transformer

    Transformer sizing

    A transformer is sized on apparent power, and its impedance decides both the voltage sag and the fault current everything downstream has to survive. This converts the load to kVA, rounds to a standard rating, and reports the currents, regulation, losses and fault level for that size.

    Loading74%Efficiency98.89%Inrush1.083e+4 A
    Selected transformer
    750.0 kVA
    556 kVA of load, 694 kVA required
    Secondary full-load current
    902 A
    at 480 V, 3-phase
    Fault current
    15.7 kA
    at 5.75% impedance — this sizes the switchgear
    Voltage regulation
    3.43%
    16.5 V drop at full load, pf 0.90
    Sizing and loading
    Apparent power first, then current, then the impedance consequences downstream.
    750 kVA
    Sizing and loading
    QuantityValueNote
    Connected load500 kWat pf 0.90
    Load apparent power555.6 kVAkW ÷ power factor
    Demand factor1.00Diversity across the connected load
    Spare capacity25%Room for growth
    Required rating694.4 kVABefore rounding to a standard size
    Selected rating750.0 kVANext standard dry-type size
    Loading at demand74%Design aim is 70–80%
    Primary current31.4 Aat 1.380e+4 V
    Secondary current902 Aat 480 V
    Full-load current check902 AI = kVA × 1000 / (√3 V)
    Percent resistance0.95%from %Z and X/R = 6.0
    Percent reactance5.67%√(%Z² − %R²)
    Voltage regulation3.43%ASA approximation
    Voltage drop at full load16.5 VRegulation × secondary voltage
    Symmetrical fault current1.569e+4 ASecondary FLA ÷ (Z%/100)
    Magnetising inrush1.083e+4 AAbout 12× full-load current, first cycle
    No-load loss1200 WConstant whenever energised
    Load loss at demand4390 WScales with the square of loading
    Total losses5590 WCore plus winding
    Efficiency98.89%Output ÷ (output + losses)

    The fault current is what the secondary switchgear has to interrupt, and it comes straight from the impedance. A lower-impedance transformer is more efficient but demands more expensive breakers downstream.

    Inspect the model
    Choose a quick result view, a scaled comparison, or the complete diagnostic set.
    Required kVA against load
    Linear in kilowatts, with the slope set by the power factor. A pf of 0.8 needs 25% more kVA than the same kW at unity.
    Required kVA against load0.000298.67597.33896.001194.671493.335050150150250250350350450450550550650650750750850850950950105010501150115012001200kVA
    Efficiency against load
    Efficiency peaks where the copper loss equals the core loss, usually around 40–60% of rating.
    Efficiency against load0.00022.2844.5666.8489.12111.395050150150250250350350450450550550650650750750850850950950105010501150115012001200Percent
    Canonical equations
    The exact relationships implemented by this engine.

    S = P / cos φ · The reason kVA, not kW, sizes the transformer.

    I = S / (√3 V) · Three-phase; drop the √3 for single-phase.

    I_sc = I_FL / (Z%/100) · Infinite-bus assumption, symmetrical RMS.

    %R cos φ + %X sin φ + (%X cos φ − %R sin φ)²/200 · ASA approximation, good to a few tenths.

    engineering methodology

    A clear path from inputs to results.

    A transformer is sized on apparent power, not on the load's nameplate kilowatts, and its impedance decides both the voltage sag and the fault current everything downstream has to survive. This converts the load to kVA, rounds to a standard rating, and reports the currents, regulation, losses and fault level for that size.

    Step-by-step methodWorked exampleAssumptions explained

    How to use

    1. Enter the connected load in kW and the load power factor.
    2. Set the demand factor and the spare capacity you want to leave.
    3. Enter the primary and secondary voltages and whether the service is single or three-phase.
    4. Add the percent impedance and X/R ratio from the nameplate.
    5. Read the selected rating, the currents, the regulation and the fault current.

    The formula

    S=Pcos⁡φ  ;  I=S3 V  ;  Isc=IFLZ%/100S = \frac{P}{\cos\varphi} \;;\; I = \frac{S}{\sqrt{3}\,V} \;;\; I_{sc} = \frac{I_{FL}}{Z\%/100}

    Reference: ANSI C57 and IEEE C57.12 for ratings and impedance; the ASA regulation approximation from IEEE Std 141 (Red Book).

    Worked example

    500 kW at 0.9 power factor, 13.8 kV to 480 V

    Inputs
    • Connected load 500 kW at pf 0.90, demand factor 1.0.
    • 25% spare capacity.
    • 13,800 V primary, 480 V secondary, three-phase.
    • 5.75% impedance, X/R of 6, 1,200 W no-load and 8,000 W load loss.
    Calculation path
    1. 1

      Apparent power is 500 / 0.90 = 555.6 kVA.

    2. 2

      With full demand and 25% spare, the required rating is 694.4 kVA.

    3. 3

      The next standard dry-type size is 750 kVA.

    4. 4

      Secondary full-load current is 750,000 / (√3 × 480) = 902 A; the primary is 31.4 A.

    5. 5

      Fault current is 902 / 0.0575 = 15,689 A, or 15.7 kA symmetrical.

    6. 6

      Regulation at 0.9 pf is 3.43%, so the secondary sags 16.5 V at full load.

    7. 7

      Losses are 1,200 W of core plus 4,390 W of copper at 74% loading, giving 98.89% efficiency.

    Result

    750 kVA · 902 A secondary · 15.7 kA fault · 3.43% regulation · 98.89% efficiency.

    Interpreting the result

    The selected size is 74% loaded at demand, which is where a distribution transformer should sit: enough headroom for a motor start and for growth, without paying for copper that never gets used. The fault current is the number the downstream switchgear is bought against, and it comes straight from the impedance — a more efficient, lower-impedance transformer is a more expensive breaker.

    Assumptions & limitations

    • The load is modelled at a single power factor; a mixed load should be summed in kW and kVAR and converted once.
    • The standard sizes are the common dry-type distribution ratings and may differ from a specific manufacturer's catalogue.
    • Fault current uses the infinite-bus assumption, which ignores source impedance and is therefore conservative.
    • Regulation uses the ASA approximation, accurate to a few tenths of a percent for distribution transformers.
    • Efficiency uses the stated no-load and load losses, scaled with the square of loading.
    • Harmonics, inrush duration, temperature rise and altitude derating are not modelled.

    Frequently asked questions

    Why is a transformer rated in kVA and not kW?

    Because the winding losses depend on current, and current depends on apparent power. The insulation and conductor sizing are set by the voltage and current, not by how much of that current does useful work, so the rating has to be in kVA.

    Why does lower impedance mean higher fault current?

    Because the fault current is the full-load current divided by the per-unit impedance. A 4% transformer passes 25 times its rated current into a bolted fault; a 6% one passes 16.7 times. Lower impedance also means better regulation, so it is a direct trade against switchgear cost.

    How accurate is the regulation formula?

    The ASA approximation is good to a few tenths of a percent for distribution transformers at typical power factors. It becomes less accurate at very low power factors, where the reactive term dominates and the exact phasor solution should be used.

    What loading should I design for?

    70–80% at demand is the usual target. Below 50% you have paid for capacity you are not using and the transformer runs at poor efficiency; above 90% there is no headroom for a motor start, and the winding runs hotter than its insulation class wants.

    What is the inrush current?

    The magnetising current on energisation, typically 8–12 times full-load current for the first cycle or two, decaying within a few cycles. It is why the primary protective device has to be sized for inrush rather than for full load.

    Does altitude affect the rating?

    Yes. Above about 1,000 m the thinner air reduces cooling, so a transformer has to be derated — typically 0.3–0.5% per 100 m above the threshold, depending on the insulation class. The model does not apply that derating.

    Methodology last reviewed 2026-10-21. Results are informational and not financial or engineering advice — see our disclaimer.