    Structural / timber

    Timber beam design

    A sawn-lumber beam is designed by adjusting a published reference stress through a chain of factors and then checking bending, shear, deflection and bearing against it. This runs the whole NDS allowable-stress chain, including the beam stability factor that applies whenever the compression edge is free to move sideways.

    Fb adjusted963 psiStability CL1.000Size factor CF1.10
    Bending
    42%
    404 psi against 963 psi allowable
    Deflection at L/360
    29%
    0.118 in actual
    Governs
    Bending
    allowable load 81 plf
    Verdict
    Passes
    all four checks within unity
    Adjustment chain and design checks
    Every factor in the NDS chain, then the four checks that decide the member.
    42%
    Adjustment chain and design checks
    QuantityValueNote
    Species and gradeDouglas Fir-Larch No. 2NDS Supplement Table 4A, No. 2
    Reference Fb875 psi12-inch-deep, normal duration, dry
    Load duration CD1.00Table 2.3.2
    Size factor CF1.10Table 4A, by nominal depth
    Volume factor CV1.000beams 5 in and deeper
    Repetitive factor Cr1.00three or more members at 24 in or less
    Beam stability CL1.000compression edge braced
    Adjusted Fb963 psithe product of all of the above
    Section modulus S21.39 in³bd²/6
    Moment of inertia I98.9 in⁴bd³/12
    Moment M8640 lb-inwL²/8
    Bending stress fb404 psi42% of allowable
    Shear V240 lbwL/2
    Shear stress fv25.9 psi25% of allowable
    Deflection0.118 inlimit 0.400 in
    Bearing stress46 psi7% of Fc⊥
    Allowable uniform load81 plfgoverned by bending

    The stability factor is the one people skip. It only applies when the compression edge is unbraced, but when it does apply it can cut the allowable bending stress by half — which is exactly the case for a beam whose top edge is free to move sideways.

    Inspect the model
    Choose a quick result view, a scaled comparison, or the complete diagnostic set.
    Allowable load against span
    Falls faster than 1/span because bending goes with the square and deflection with the fourth power.
    Allowable load against span0.00036.0972.17108.26144.35180.446 ft6 ft8 ft8 ft10 ft10 ft12 ft12 ft14 ft14 ft16 ft16 ft18 ft18 ft20 ft20 ft22 ft22 ft24 ft24 ftplf
    Utilisation by check
    Anything at or above 100% governs the design; the largest bar is the one to fix.
    Utilisation by check0.0009.9019.8129.7139.6249.5241.97BendingBending24.83ShearShear29.47DeflectionDeflection7.31BearingBearingPercent
    Canonical equations
    The exact relationships implemented by this engine.

    fb = M/S ≤ Fb′ · Fb′ = Fb·CD·CF·CV·CL·Cr

    fv = 3V/2bd ≤ Fv′ · Parabolic distribution, maximum at mid-depth.

    Δ = 5wL⁴/384EI · L/360 for floor live load, L/240 for total load.

    CL from FbE = 1.20E′min/(Rb)² · NDS 3.3.3, with Rb = √(le·d/b²).

    engineering methodology

    A clear path from inputs to results.

    A sawn-lumber beam is designed by taking a published reference stress, multiplying it through a chain of adjustment factors, and then checking bending, shear, deflection and bearing against the result. This runs the whole NDS allowable-stress chain, including the beam stability factor that applies whenever the compression edge is free to move sideways.

    Step-by-step methodWorked exampleAssumptions explained

    How to use

    1. Choose the species and grade, which set the reference stresses.
    2. Enter the member size, span and uniform load.
    3. Pick the load duration and say whether it is a repetitive member.
    4. Set the unbraced length of the compression edge and the bearing length.
    5. Read the four utilisation checks and the allowable load.

    The formula

    fb=MS≤Fb′  ;  Fb′=Fb CDCFCVCLCr  ;  Δ=5wL4384EIf_b = \frac{M}{S} \le F_b' \;;\; F_b' = F_b\,C_D C_F C_V C_L C_r \;;\; \Delta = \frac{5wL^4}{384EI}

    Reference: NDS for Wood Construction (AWC), §3.3 and Tables 2.3.2, 4A and 4.3.1; reference values from the NDS Supplement.

    Worked example

    2×10 Douglas Fir-Larch No. 2 over 12 ft at 40 plf

    Inputs
    • 1.5 × 9.25 in member, 12 ft span, 40 plf uniform load.
    • Douglas Fir-Larch No. 2, normal load duration.
    • Compression edge continuously braced, 3.5 in bearing.
    • Deflection limit L/360.
    Calculation path
    1. 1

      Section modulus is 1.5 × 9.25² / 6 = 21.4 in³ and moment of inertia is 98.9 in⁴.

    2. 2

      The simple-span moment is 40 × 144 × 12 / 8 = 8,640 lb-in, and the shear is 240 lb.

    3. 3

      Size factor CF for a 9.25 in depth is 1.1; the volume factor is 1.0 at this span; the member is braced so CL is 1.0.

    4. 4

      Adjusted Fb is 875 × 1.0 × 1.1 = 963 psi, and the applied bending stress is 8,640 / 21.4 = 404 psi — 42% of allowable.

    5. 5

      Deflection is 0.118 in against a limit of 0.400 in, so it uses 29% of its allowance.

    6. 6

      Bending governs, and the allowable uniform load is 81 plf against the 40 plf applied.

    Result

    42% bending · 29% deflection · 81 plf allowable · bending governs.

    Interpreting the result

    The governing check is the one to fix. Here bending governs, so a deeper member or a shorter span helps immediately; if deflection governed, a stiffer species or a deeper member would be the only levers. The stability factor is the one people skip — it only applies when the compression edge is unbraced, but when it does it can halve the allowable bending stress.

    Assumptions & limitations

    • Visually graded sawn lumber, No. 2 grade, dry service, normal temperature.
    • Reference values are from the NDS Supplement Table 4A and apply to a 12-inch-deep member under normal-duration load.
    • Emin is taken as 0.35E, the published ratio for this grade, for the stability calculation.
    • Simply supported, uniformly loaded, with the load applied to the top edge.
    • Wet service, fire-retardant treatment, incising and elevated temperature each carry their own factor and are not modelled.
    • Deflection is bending deflection only; shear deflection is negligible at these span-to-depth ratios.

    Frequently asked questions

    Why is the allowable bending stress higher than the reference value?

    Because of the size factor. A 2×10 is stronger per square inch in bending than a 12-inch-deep reference member, and CF captures that. The volume factor and the stability factor then pull it back down for long or unbraced members.

    When does the beam stability factor apply?

    When the compression edge is not continuously braced against lateral movement — a beam whose top edge is free to translate sideways. It does not apply to a joist with decking screwed to it, which is why floor joists rarely use it and headers often do.

    Can I use this for engineered lumber?

    Not directly. LVL, glulam and I-joists have their own reference values and their own adjustment factors, published by the manufacturer. Use this for solid sawn lumber only.

    What does the load duration factor do?

    Wood carries more load for a short time than for a long one. Snow gets 1.15, wind and seismic 1.6, and permanent load 0.9. It is the reason a roof can be designed for a snow load that would fail it if applied every day.

    Should I design to L/360 or L/240?

    L/360 for live load under floors, L/240 for total load, and L/180 where finishes are not sensitive. The limit is about what the finishes above can tolerate, not about safety — a beam can pass bending and still crack plaster.

    Methodology last reviewed 2026-10-21. Results are informational and not financial or engineering advice — see our disclaimer.