    Process / relief systems

    Two-phase relief sizing

    A relief valve on a liquid-filled vessel does not relieve liquid: as the pressure drops through the seat the liquid flashes, and the flow becomes two-phase. The mixture is far bulkier than the liquid, so the valve that would be right for liquid service is far too small — often by a factor of four.

    OrificeFServiceFlashingP1180 psia
    Required area
    0.280 in²
    orifice F
    Critical mass flux
    7,701 kg/m²·s
    ω = 9.1
    Liquid-only answer
    0.069 in²
    what the incompressible equation would give
    Undersizing
    4.0×
    the factor the liquid method would be wrong by
    The omega method
    One parameter captures the whole flashing behaviour, and it is 9.1 for saturated water.
    F orifice
    The omega method
    TermValueNote
    Set pressure150 psigas entered
    Relieving pressure179.7 psia110% of set plus atmosphere
    Relieving pressure1239 kPafor the mass-flux expression
    Inlet specific volume0.001000 m³/kgsaturated liquid
    Omega9.10the flashing value, 9.1
    Critical mass flux7,701 kg/m²·sG = 0.66 √(P₁/v₀ω)
    Required flow5,000 kg/has entered
    Required area0.280 in²effective orifice
    Liquid-only area0.069 in²the wrong answer
    Selected orificeF — 0.307 in²API 526

    The two-phase area is 4.0 times the liquid-only answer. Sizing this service as a liquid is the classic error: the valve would be undersized by that factor and would not protect the vessel.

    Inspect the model
    Choose a quick result view, a scaled comparison, or the complete diagnostic set.
    Required area against set pressure
    Higher set pressure means a higher mass flux, so a smaller orifice for the same flow.
    Required area against set pressure0.0000.1010.2010.3020.4020.50350 psig50 psig100 psig100 psig150 psig150 psig250 psig250 psig400 psig400 psigin²
    Two-phase against liquid
    The liquid equation is not conservative here — it is simply wrong, by this factor.
    Two-phase against liquid0.0000.0660.1320.1980.2640.3300.069Liquid methodLiquid method0.280Two-phaseTwo-phasein²
    Canonical equations
    The exact relationships implemented by this engine.

    ω = 9.1 · Saturated liquid that flashes.

    G = 0.66 √(P₁/(v₀ ω)) · Critical (choked) flow.

    A = W/G · Effective orifice.

    A = Q/(38 K_d √ΔP) · What not to use.

    engineering methodology

    A clear path from inputs to results.

    A relief valve on a liquid-filled vessel does not relieve liquid: as the pressure drops through the seat the liquid flashes, and the flow becomes two-phase. The mixture is far bulkier than the liquid, so the valve that would be right for liquid service is far too small.

    Step-by-step methodWorked exampleAssumptions explained

    How to use

    1. Set the pressure and the required relieving rate.
    2. Choose the inlet condition — saturated liquid is the common case.
    3. Enter the discharge coefficient.
    4. Read the required area and the API 526 orifice.

    The formula

    G=0.66P1v0 ω,ω=9.1G = 0.66\sqrt{\frac{P_1}{v_0\,\omega}}, \quad \omega = 9.1

    Reference: API 520 Part I Appendix C, the omega method for flashing service.

    Worked example

    5,000 kg/h of saturated water at a 150 psig set pressure

    Inputs
    • 150 psig set, 5,000 kg/h.
    • Saturated liquid inlet, discharge coefficient 0.65.
    Calculation path
    1. 1

      The relieving pressure is 110% of set plus atmosphere: 179.7 psia, or 1,239 kPa.

    2. 2

      With ω = 9.1 and v₀ = 0.001 m³/kg, the critical mass flux is 7,700 kg/m²·s.

    3. 3

      The required flow of 1.39 kg/s therefore needs 1.8 cm², or 0.28 in².

    4. 4

      The liquid-only equation would have given 0.07 in² — four times too small.

    5. 5

      The next API 526 orifice is F at 0.307 in².

    Result

    0.28 in² · F orifice · 4× the liquid answer.

    Interpreting the result

    Sizing a flashing service with the liquid equation is the classic error: the valve looks adequate on paper and is undersized by a factor of four in service, which is exactly when it matters. The omega method exists because the flashing cannot be ignored.

    Assumptions & limitations

    • A saturated liquid inlet that flashes through the seat.
    • Critical (choked) flow, which applies for ω above about 4.
    • A conventional valve with a 0.65 discharge coefficient.
    • No inlet or outlet piping loss.

    Frequently asked questions

    Why does the liquid flash?

    Because the pressure at the valve seat is below the vapour pressure at the inlet temperature, so the liquid boils as it accelerates through the orifice.

    Why is the two-phase area so much larger?

    Because the mass flux is far lower — the mixture occupies much more volume than the liquid, so the same mass flow needs a much bigger hole.

    Does the same apply to a steam trap?

    Yes — a trap discharging condensate flashes in exactly the same way, which is why a trap is sized on the flash steam volume rather than the condensate flow.

    What is omega?

    A single dimensionless parameter that captures the flashing behaviour. It is 9.1 for saturated water, and larger means more flashing and a lower mass flux.

    Is the flow always choked?

    For a flashing service, usually. If ω is below about 4 the flow may be subcritical and a different expression applies.