    Power systems / Protection

    Protective device coordination

    Will the downstream breaker clear before the upstream one? Enter two devices and the fault current, and compare their IEC 60255 curves: trip times, the margin between them, and the TMS the upstream device needs to be selective.

    Fault current4.00 kAUpstream TMS0.30SelectivityPass
    Downstream trip
    0.18 s
    40.0× pickup
    Upstream trip
    0.74 s
    16.0× pickup
    Margin
    4.03×
    Required 1.30×
    Verdict
    Selective
    Both devices see the fault
    Coordination at the fault
    Trip times from the IEC 60255 curve, and the margin between them.
    Coordination at the fault
    DeviceCurvePickup (A)TMSTime at fault (s)
    UpstreamStandard inverse2500.300.737
    DownstreamStandard inverse1000.100.183

    Selective: the upstream device waits 4.03× the downstream time at 4000 A.

    Inspect the model
    Choose a quick result view, a scaled comparison, or the complete diagnostic set.
    Time-current curves
    Trip time against current. The upstream curve must sit above the downstream one at the fault.
    Time-current curves0.0009.6419.2728.9138.5548.180.3k0.3k0.3k0.3k0.5k0.5k0.6k0.6k0.8k0.8k1.0k1.0k1.4k1.4k1.8k1.8k2.4k2.4k3.1k3.1k4.1k4.1k5.3k5.3k7.0k7.0k9.2k9.2k12.2k12.2k16.0k16.0kUpstreamDownstream
    Canonical equations
    The exact relationships implemented by this engine.

    t = TMS · 0.14 / ((I/Is)^0.02 − 1) · Standard inverse; VI, EI and LTI use different constants.

    m = t_upstream / t_downstream · Typically 1.3 or more at the maximum fault level.

    TMS_up = TMS_up,now · m_required / m_actual · What the upstream device needs to reach the margin.

    engineering methodology

    A clear path from inputs to results.

    Coordination is the question a cable check cannot answer: at this fault current, does the downstream device clear before the upstream one? Two IEC 60255 curves, one fault level, and the margin between them — plus the TMS the upstream device would need to be selective.

    Step-by-step methodWorked exampleAssumptions explained

    How to use

    1. Set the downstream curve, pickup and TMS.
    2. Set the upstream device the same way.
    3. Enter the fault current and the margin you require, then read the verdict.

    The formula

    t=TMS⋅0.14(I/Is)0.02−1,m=tuptdownt = \frac{TMS \cdot 0.14}{(I/I_s)^{0.02} - 1}, \qquad m = \frac{t_{up}}{t_{down}}

    Reference: IEC 60255-151 standard inverse curve; margin convention from common protection practice.

    Worked example

    100 A downstream, 250 A upstream, 4 kA fault

    Inputs
    • Both standard inverse; downstream TMS 0.10, upstream TMS 0.30.
    Calculation path
    1. 1

      At 4 kA the downstream sees 40× pickup and trips in 0.13 s; the upstream sees 16× and trips in 0.44 s.

    Result

    Margin 3.4×, comfortably selective against a 1.3× requirement.

    Interpreting the result

    A margin below the requirement means a fault in the downstream zone can trip the upstream device, taking out more of the installation than necessary.

    Assumptions & limitations

    • Two devices at one fault level.
    • IEC inverse curves; definite-time relays are handled separately.
    • No CT saturation, no arc impedance.
    • Only the maximum fault level is checked here.

    Frequently asked questions

    Why 1.3×?

    It covers breaker clearing time, relay tolerance and the CT error; some utilities ask for 1.5×.

    What does the suggested TMS do?

    It is the upstream TMS that would produce the required margin at this fault current.

    Should I check the minimum fault too?

    Yes — selectivity at the maximum fault does not guarantee it at the minimum, where the curves are closer.

    Can I coordinate a fuse and a relay?

    Not in this form; fuse curves are manufacturer-specific and need the published time-current data.