Motor full-load current and branch protection
Article 430 is built on table values, not nameplate values. The full-load current comes from Table 430.250 or 430.248, and every downstream decision — conductor, overload, short-circuit protection, controller — is a percentage of that table number. Sizing from the nameplate is the most common error in a motor circuit, and it fails inspection because the code says the table governs.
| Item | Value | Rule |
|---|---|---|
| Motor | 10 hp, 3-phase, 460 V | as entered |
| Full-load current | 14.0 A | Table 430.250 |
| Branch conductors | 17.5 A | 125% of FLA, §430.22 |
| Overload target | 17.5 A | 125% (SF ≥ 1.15) |
| Overload maximum | 19.6 A | §430.32(C) |
| Controller rating | 17.5 A | 125% of FLA, §430.83 |
| Protection target | 35.0 A | 250% of FLA, Table 430.52 |
| Standard device | 35 A | next size up, §240.6 |
| Ceiling if it trips | 56.0 A | 430.52 Exception No. 1 |
A 10 hp 3-phase motor at 460 V draws 14 A from the table. Conductors are sized at 125% of that, and the overload is set between 17.5 A and 19.6 A.
Table 430.250 / 430.248 · By horsepower and voltage.
1.25 × FLA · §430.22.
1.25 or 1.15 × FLA · By service factor, §430.32.
multiplier × FLA · Table 430.52, then next standard size.
A clear path from inputs to results.
Article 430 is built on table values, not nameplate values. The full-load current comes from Table 430.250 or 430.248, and every downstream decision — conductor, overload, short-circuit protection, controller — is a percentage of that table number.
How to use
- Choose the horsepower, phases and voltage.
- Set the service factor, which selects the overload rule.
- Pick the branch protection type.
- Read the FLA and the four derived ratings.
The formula
Reference: NFPA 70 Article 430: Table 430.250 and 430.248 for FLA, §430.22, §430.32, §430.52 and §430.83.
Worked example
10 hp at 460 V, three phase
- 10 hp, three phase, 460 V.
- Service factor 1.15.
- Inverse-time breaker protection.
- 1
Table 430.250 gives 14 A for a 10 hp motor at 460 V.
- 2
Branch conductors are 125% of that, or 17.5 A.
- 3
With a 1.15 service factor the overload is set at 125%, also 17.5 A, with a ceiling of 140% or 19.6 A.
- 4
A breaker is sized at 250% of FLA, or 35 A, which is already a standard rating.
- 5
The controller is rated at 125%, or 17.5 A.
14 A FLA · 17.5 A conductors · 17.5 A overload · 35 A breaker.
Interpreting the result
The protection device is sized far above the full-load current because it only has to survive the starting current — typically six times FLA for a few seconds. The overload, by contrast, is set just above the running current, because that is what protects the motor from sustained overheating.
Assumptions & limitations
- Table values are for ordinary induction motors at the listed voltages.
- The service factor selects the 125% or 115% overload rule.
- The branch device is the standard size; the 430.52 ceiling is reported separately.
- No motor circuit protector, soft starter or drive is modelled.
Frequently asked questions
Why not use the nameplate current?
Because §430.6(A)(1) says the table governs for conductor and protection sizing. The nameplate is only used when the motor is not listed in the table.
Why 250% for a breaker?
Because a motor draws roughly six times its full-load current while starting, and the breaker must not trip on that. The overload handles the running condition.
Does a VFD change this?
Yes — a drive limits starting current, so the branch protection is sized to the drive input rather than the motor table, and the rules move to Article 430 Part X.
What is the difference between overload and branch protection?
The overload protects the motor from sustained overcurrent; the branch device protects the conductors from short circuit. They are sized from different percentages and neither replaces the other.
What if the standard breaker trips on start?
430.52 Exception No. 1 allows the next size up, up to 400% for a breaker or 225% for a dual-element fuse, provided the conductors still protected.