Heat loss calculator
A heating load is two numbers added together: conduction through the envelope and the energy needed to warm incoming air. This calculator applies the U·A·ΔT and 0.33·ACH·V·ΔT expressions, splits the two contributions, and sizes the plant with a distribution allowance.
| Term | Watts |
|---|---|
| Fabric U·A·ΔT | 1800 |
| Ventilation 0.33·ACH·V·ΔT | 2475 |
| Total | 4275 |
| Per m² of envelope | 21 |
Steady-state at design outdoor temperature. Thermal bridging and solar gains are not included.
Q = U·A·ΔT · Steady-state conduction through the envelope.
Q = 0.33·ACH·V·ΔT · 0.33 Wh/m³K is the volumetric heat capacity of air.
Q_total = Q_fabric + Q_vent · Add distribution losses for plant sizing.
A clear path from inputs to results.
A heating load is two numbers added together: conduction through the envelope and the energy needed to warm incoming air. This calculator applies the U·A·ΔT and 0.33·ACH·V·ΔT expressions, splits the two contributions, and sizes the plant with a distribution allowance.
How to use
- Enter the area-weighted U-value and envelope area.
- Set the design temperature difference.
- Enter the heated volume and air change rate.
- Read the design load and the plant size.
The formula
Reference: CIBSE and ASHRAE steady-state heating load method.
Worked example
200 m² at U 0.30, ΔT 30 K, 500 m³ at 0.5 ACH
- Envelope 200 m², U 0.30 W/m²K.
- ΔT 30 K.
- Volume 500 m³, 0.5 air changes per hour.
- 1
Fabric: 0.30 × 200 × 30 = 1,800 W.
- 2
Ventilation: 0.33 × 0.5 × 500 × 30 = 2,475 W.
- 3
Total: 4,275 W, or 4.28 kW.
- 4
At 90% efficiency the boiler needs about 4.75 kW.
4.28 kW design load · 1.80 kW fabric · 2.48 kW ventilation.
Interpreting the result
Ventilation often exceeds fabric loss in a well-insulated building, which is why airtightness and heat recovery matter more than extra insulation once the envelope is good. The split chart makes that visible immediately.
Assumptions & limitations
- Steady-state at design outdoor temperature.
- No solar or internal gains.
- Thermal bridging included in the U-value.
- No thermal mass or intermittent heating effects.
Frequently asked questions
Should I use the external or internal area?
Use the area the U-value was calculated for, usually the external envelope.
Does this size a heat pump?
It gives the design load; heat pump selection also needs the flow temperature and emitter output.
What is a typical ACH?
0.3–0.5 for a modern airtight house, 1–2 for older housing.
Methodology last reviewed 2026-10-21. Results are informational and not financial or engineering advice — see our disclaimer.