Grounding grid calculator
A substation earthing design is a voltage comparison, not a resistance target: the ground potential rise during a fault must stay below the touch voltage a person can survive. This gives the IEEE 80 limits, the grid resistance and the rise, plus the cable pulling tension for the same job.
| Quantity | Value | Unit |
|---|---|---|
| Surface derating Cs | 0.700 | — |
| Step voltage limit | 2231 | V |
| Touch voltage limit | 681 | V |
| Grid resistance | 0.991 | Ω |
| Ground potential rise | 4953 | V |
| Pull tension out | 8.47 | kN |
| Sidewall pressure | 4.24 | kN/m |
GPR = Ig·Rg must stay below the touch voltage limit; mesh voltage needs the full Km/Ki calculation.
E_touch = (1000 + 1.5·Cs·ρs)·0.116/√ts · IEEE 80, 50 kg body.
E_step = (1000 + 6·Cs·ρs)·0.116/√ts · Six times the surface resistance term.
Rg = ρ/(4√A) + ρ/L · Simplified Schwarz form.
A clear path from inputs to results.
A substation earthing design is a voltage comparison, not a resistance target. During a fault the whole grid rises above remote earth, and what matters is whether that rise exceeds the touch voltage a person standing on the surface can survive.
How to use
- Enter the soil resistivity and the surface layer.
- Set the fault current, clearing time and grid geometry.
- Compare the ground potential rise with the touch limit; check the cable pulling tension below.
The formula
Reference: IEEE 80 §8 step and touch criteria; simplified Schwarz grid resistance.
Worked example
1,000 m² grid in 100 Ω·m soil, 5 kA, 0.5 s
- 100 mm of 3,000 Ω·m crushed rock on the surface.
- 1
Cs = 0.70. Touch limit = (1000 + 1.5 × 0.7 × 3000) × 0.116/√0.5 = 681 V. Rg = 100/(4√1000) + 100/500 = 0.99 Ω. GPR = 4,950 V.
GPR 4,950 V against a 681 V touch limit — the grid fails and needs more conductor.
Interpreting the result
Adding buried conductor lowers Rg only slowly — the ρ/(4√A) term dominates — which is why the practical fix is usually a surface layer of crushed rock rather than more copper.
Assumptions & limitations
- Step and touch only; mesh voltage needs the full IEEE 80 Km/Ki calculation.
- Cs valid for a surface layer up to 0.3 m.
- Uniform soil resistivity.
- Conductor sizing to §11 is a separate adiabatic check.
Frequently asked questions
Why is the touch limit lower than the step limit?
The step path goes foot to foot through the earth, so the surface layer resistance is counted six times instead of 1.5.
What is Cs?
The derating factor for a thin surface layer; it approaches 1 as the layer gets thicker.
Does a lower resistance always help?
It lowers the GPR, but the limits move with the surface layer, so both sides matter.
Can I use this for a building earth?
The voltage limits apply, but a building electrode is not a grid and needs the relevant standard for its earthing arrangement.
Methodology last reviewed 2026-10-22. Results are informational and not financial or engineering advice — see our disclaimer.